Instrumentation Cables – Braided / Armoured

Applications

Can be used in cable tray or conduit to connect electrical instrumentation and communication circuits in industrial process controls, refineries, oiland gas plants.

Multipair Individual and Overall Screen

Not armoured

  • PE/IS/OS/PVC
  • XLPE/IS/OS/LSZH

Armoured

  • PE/IS/OS/PE/SWA/PVC
  • XLPE/IS/OS/LSZH/SWA/LSZH
BS 5308 (300/500 V)
Unarmoured Armoured
Cross section (mm2) Outer diame- eter (mm) Weight (kg/km) Diameter under armour (mm) Outer diame- eter (mm) Weight (kg/km) Capacitance (pF/m) L/R (μH/Ohm)
0,5 mm2 solid U-PE/IS/OS/PVC U-PE/IS/OS/PE/SWA/PVC
2x2x0,5 10,3 150 10,3 14,9 380 115 25
5x2x0,5 13,5 250 13,5 19,0 640 115 25
10x2x0,5 18,3 380 18,3 24,2 890 115 25
15x2x0,5 1,1 490 21,1 27,7 1350 115 25
20x2x0,5 3,5 640 23,5 30,3 1470 115 25
30x2x0,5 7,9 970 27,9 34,9 1870 115 25
50x2x0,5 36,1 1470 36,1 44,5 3000 115 25
0,5 mm2 flexible F-PE/IS/OS/PVC F-PE/IS/OS/PE/SWA/PVC
2x2x0,5 12,0 100 12,0 16,8 460 115 25
5x2x0,5 15,2 250 15,2 20,9 760 115 25
10x2x0,5 1,1 480 21,1 27,9 1300 115 25
15x2x0,5 4,5 570 24,5 31,3 1440 115 25
20x2x0,5 7,3 780 27,3 31,3 1870 115 25
30x2x0,5 32,3 1020 32,3 34,3 2400 115 25
50x2x0,5 41,7 1680 41,7 51,5 3930 115 25
1 mm2 solid U-PE/IS/OS/PVC U-PE/IS/OS/PE/SWA/PVC
2x2x1 12,8 200 12,8 17,6 515 115 25
5x2x1 16,2 290 16,2 21,9 950 115 25
10x2x1 ,6 580 22,6 29,4 1 330 115 25
15x2x1 6,2 780 26,2 33,2 1680 115 25
20x2x1 9,8 1010 29,8 37,8 2540 115 25
30x2x1 35,4 1430 35,4 43,8 2900 115 25
50x2x1 44,9 2360 44,9 54,9 4800 1 15 25
1,5 mm2 stranded R-PE/IS/OS/PVC R-PE/IS/OS/PE/SWA/PVC
2x2x1,5 14,7 250 14,7 20,4 730 120 40
5x2x1,5 18,8 460 18,8 25,4 1180 120 40
10x2x1,5 6,5 760 26,5 33,5 1820 120 40
15x2x1,5 30,8 1020 30,8 38,8 2350 120 40
20x2x1,5 34,4 1350 34,4 42,6 3030 120 40
30x2x1,5 41,0 1900 41,0 50,8 4050 120 40
50x2x1,5 52,2 3060 52,2 62,6 5960 120 40
Applicable Standards Minimum bending radius Operating temperature
BS 5308 or EN 50288-7 Basic design

Not armoured type:

12 times the outer diameter (for conductors class 1 and class 2); 10 times the outer diameter (for conductors class 5).

Armoured type:

15 times the outer diameter.

-20 °C to +80 °C (for general use);
-40 °C to +90 °C (on request).
IEC 60332-1 Flame retardant
IEC 60332-3 Fire retardant (cat. C or A according to requirements)
IEC 60754-1 Halogen free properties (only for LSZH cables)
IEC 61034-2 Low smoke emission (only for LSZH cables)
Cable construction
Conductors

Plain annealed electrolytic copper wire according to EN 60228 class 1(U) solid, class 2 (R) stranded, class 5 (F) flexible.

Insulation

PVC, PE, XLPE or LSZH thermoplastic material.

Twisting

The insulated cores shall be twisted in pairs for a good reduction of the electromagnetic noise.

Individual screen

Aluminium/polyester tape, coverage >100%, aluminium in contact with tinned copper drain wire.

Cabling

The screened pairs are cabled with suitable non hygroscopic fillers (when necessary) and wrapped with polyester tape if required.

Overall screen

Aluminium/polyester tape, coverage >100%, aluminium in contact with tinned copper drain wire.

Inner sheath

PE, PVC or LSZH thermoplastic material.

Armour

Single layer of galvanized steel wires (SWA).

Outer sheath

PVC or LSZH thermoplastic material.

Available on request

Tinned conductors. Single triad or multitriads. Galvanized steel wire braid (GSWB) or galvanized steel tape armour (GSTA). Different insulation and sheath colours. Sheath materials can be provided for excellent water, oil, hydrocarbons, UV resistance or other special performance.

Click here to download .pdf file