Mechanical and Installation Characteristics
Operating temperature (after installation) -30°C – +80°C
Electrical Characteristics
Voltage rating – 300/500 V r.m.s.
Spark test insulation – 7000 V r.m.s. / H.F.
Conductors resistance – 13.7 Ohm/km (at 20°C in d.c.) for 1.5 mm2
8.21 Ohm/km (at 20°C in d.c.) for 2.5 mm2
5.09 Ohm/km (at 20°C in d.c.) for 4 mm2
3.39 Ohm/km (at 20°C in d.c.) for 6 mm2
Insulation resistance – 1000 MOhmxkm (at 70°C in d.c.)
General Standards
For the construction – BS 6500
For the conductors – EN 60228 / IEC 60228 (class 5)
Behaviour Under Fire Conditions
Flame retardant cable (NPF) – IEC 60332-1-2, EN 50265-2-1, CEI 20-35/1-1
Fire retardant cat.C – IEC 60332-3-24, EN 50266-2-4, CEI 20-22/3-4
Corrosive acid gas (0.5% acid gas) – IEC 60754-1, EN 50267-2-1, CEI 20-37/2-1
Smoke density (Light transmittance min.60%) – IEC 61034-2, EN 50268-2, CEI 20-37/3-1